Sign In | Join Free | My chinaqualitycrafts.com
chinaqualitycrafts.com
Products
Search by Category
Home >

Total Heat Recovery 58kW Air Cooled Modular Chiller 58 kW-928 kW

Categories Air Cooled Modular Chiller
Brand Name: EuroKlimat
Model Number: EKAC 210BRLHR
Certification: ISO9001, ISO14001, OHSAS18001, CRAA, CQC
Place of Origin: China
MOQ: 1
Price: negotiation
Payment Terms: L/C, T/T
Supply Ability: 3000 pcs per month
Delivery Time: 20 working days after received your payment
Packaging Details: Carton
Product Name: Low-temp high-efficiency total heat recovery modular air cooled heat pump unit
Limiting Temperature: -20 ℃ Cooling and 48℃ Heating
Cooling capacity range: 58 kW~928 kW
Heating capacity range: 63 kW~1008 kW
COP: 3.48
IPLV: 8.85
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    Total Heat Recovery 58kW Air Cooled Modular Chiller 58 kW-928 kW


    Low-temp high-efficiency model Air-cooled Heat Hump Unit


    Specifications:


    Technical data sheet


    Model EKAC
    210BRLHR
    EKAC
    420BRLHR
    EKAC
    360BRLHR
    EKAC
    840BRLHR
    EKAC
    1050BRLHR
    EKAC
    1260BRLHR
    Air conditioning modeNominal cooling capacitykW58116174232290348
    Nominal heating capacitykW63126189252315378
    Total power of nominal cooling capacitykW163248648096
    Total power of nominal heating capacitykW1734516885102
    Water flow rate for nominal
    cooling capacity
    3
    m /h
    102030405060
    Water flow rate for nominal
    heating capacity
    3
    m /h
    10.821.632.443.254.064.8
    Hot water modeNominal water flowm3/h13.226.439.652.86679.2
    Nominal heating capacitykW77154231308385462
    Total power of nominal heating capacitykW1938577695114
    Cooling + Heat recovery modeNominal cooling capacitykW57114171228285342
    Nominal heat recovery capacitykW70.5141.0211.5282.0352.5423.0
    Total nominal powerkW13.527.040.554.067.581.0
    Nominal water supply capacity at heat recovery side3
    m /h
    13.226.439.652.866.079.2
    Nominal water flow at
    evaporator side
    3
    m /h
    10.320.630.941.251.561.8
    Power supply 380V/3N~/50Hz
    Flow control Electronic expansion valve
    Refrigerant R22
    Heat exchanger
    type
    Air conditioning side braze-welded panel-type heat exchanger
    Hot water side High-efficiency bucket heat exchanger
    CompressorType High-efficiency bucket heat exchanger
    Lubricant LubricantMineral oil (SUNISO 3GS)
    Qty.Set24681012
    FanType  
    Qty.Set24681012
    Water resistanceAir conditioning sidekPa454545454545
    Hot water sidekPa656565707070
    Minimum diameter for water pipesAir conditioning sideinch≥2≥2-1/2≥3≥4≥4≥5
    Hot water sideinch≥2-1/2≥3≥4≥4≥5≥5
    DimensionsL x Hmm2012x1840
    Width 88021253370461558607015
    Power cable specificationSection area of live linemm2≥10≥35≥70≥95≥120≥150
    Qty. of live lines 3
    Section area of null linemm2≥4
    Qty. of null lines 1
    Section area of grounding linemm2≥10≥16≥35≥50≥60≥75
    Qty. of grounding lines 1
    Net weightkg61012201830244030503660
    Operation weightkg63012601890252031503780

    Note:
    ■ Air conditioning mode: Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172 m3/(h·kW);
    outdoor ambient temperature 35°C. Test conditions for nominal heating capacity: outlet water temperature: 45°C; water flow: 0.172m3/(h·kW);
    temperature of outdoor dry/wet bulb: 7°C/6°C.
    ■ Cooling + Heat recovery mode Test conditions for nominal cooling capacity: Hot water side: Outlet water temp. 45°C; nominal water flow for hot water mode.
    Air conditioning side: Outlet water temp. 7°C; nominal water flow for heating mode.
    ■ Hot water mode: Test conditions for nominal water flow: temperature of outdoor dry/wet bulb: 20/15°C; Temperature of inlet/outlet water: 50/55°C.
    ■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
    ■ Water resistance at the hot water side includes water pressure drop of the unit and does not include the pressure drop at the Y-shaped filter and other components.
    ■ Pipes outside the unit need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK does not provide the pipes.
    ■ Full heat recovery units and other units can be combined to form partial heat recovery modular system. Full heat recovery units can also be combined to form a
    total heat recovery system. Modular units can be formed using the 1~16 basic modules. The above table lists the parameters for common module combinations.


    Decription


    1. In the traditional solutions for buildings, air conditioning + hot water take up 80% of the total energy consumption. The EKAC series low-temperature highefficiency total heat-recovery unit provides cooling,
    heating, and "free" hot water. It can work around the clock to provide air conditioning and hot water with
    a temperature as high as 65°C. Tests conducted by authoritative labs indicate that the COP of the unit is
    as high as 9.44, exceeding the national standard by a long way and saving energy by as much as 60%.


    2. The unit makes full use of waste heat generated during condensation to improve the COP up to 9.44 in cooling + heat recovery mode. The COP is 3.5 times higher than traditional air conditioners and 2.5 times higher than certain heat recovery air conditioners.


    3. The unit features an innovative design, making it efficient and compact. High-efficiency heat exchanging
    tubes are used, improving the heat exchange ratio by 3.7 times compared with common tubes. Fins outside
    the tube and ridges inside the tube can generate strong turbulent flow to greatly improve the heat exchange ratio.


    4. The EKAC series low-temperature high efficiency total heat recovery modular air-cooled heat pump unit features stateof-the-art enhanced vapor injection (EVI) technologies, increasing refrigerant recycle by 20%. The evaporation capacity is improved by mid-pressure refrigerant intake. One compressor compresses refrigerant 2 times in each cycle. Half-M fins are used to improve the heat-exchange efficiency of the heat exchanger. The unit features state-of-the-art cross diagonal convection angles for stainless steel braze-welded panel-type heat exchanger and stainless steel braze-welded panel-type economizer (used to increase the enthalpydifferentiation between the inlet and outlet of the evaporator). An EXV is used to precisely control the operation of the unit


    5. The EKAC low-temperature high-efficiency modular aircooled heat pump unit features excellent heating COP when the ambient temperature is low (20% higher than common air-cooled heat pump unit when the ambient temperature is -10°C). The lower ambient temperature limit is expanded from -10°C of common units to -20°C. This greatly improves cooling performance in areas where the winter is cold, reducing or eliminating the need for auxiliary heaters.


    6. Each modular unit has two power gears. When multiple modular units are combined, there could be many power gears. When working at a partial workload (99% of the operation time), the unit intelligently regulates the output based on the actual workload, making the operation efficiency even higher. With an optional 2-way valve water control feature, the unit can send out signals to cut off chilled water. This enables automatic flow control for pumps in line with the transducer, which helps save more energy.


    7. The EKAC series low-temperature high-efficiency total heatrecovery unit features state-of-the-art EVI enthalpy increase technologies, and can provide effective heating and sufficient hot water when the ambient temperature is as low as -20°C. The unit can provide effective heating for areas that are extremely code in winter.


    8. fast heating; hot water available as soon as you turn on the tap; absolutely safe as there is no emission of
    harmful gas and the risk of electric shock is eliminated by separating water and electricity. The central hot
    water system can provide hot water with a stable temperature for multiple outlets, making bathing comfortable.


    9. Investments can be made in installments as the project rolls out. This reduces initial investment for
    new projects and making renovation project easy to complete.


    10. Units of this series support modular connection with common air-cooled heat pump units to meet various
    heat recovery requirements


    11. Units of this series are controlled by microcomputers. Each control module can control up to 16 units, making unit combination easier. Temperature and level of water in the water tank are controlled automatically, and the water pump starts/stops automatically. No dedicated operator is required, reducing the management cost by easy smart control.

    Buy Total Heat Recovery 58kW Air Cooled Modular Chiller 58 kW-928 kW at wholesale prices
    Send your message to this supplier
     
    *From:
    *To: Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Inquiry Cart 0